Special Vertical & Lateral Load Considerations for Steel Joists & Joist Girders
Matthew
Stuart, P.E., S.E., F.ASCE
Course Outline
This one hour online course will provide the user with an understanding of the special design considerations necessary when dealing with unusual vertical and horizontal loads on steel joists and joist girders.
This course includes a multiple choice quiz at the end.
Learning Objective
At the conclusion
of this course, the student will:
- Understand the options available
when designing joists for special uniform and concentrated vertical loads.
- Understand the capacity limitations
of both joists and joist girders to resist lateral loads.
- Understand the
analysis and strengthening of standard joist and joist girder bearing assemblies
for the transfer of out-of-plane lateral loads.
Course
Introduction
Often in the
course of the design of a joist, loads in addition to uniform vertical gravity
loads are imposed on the member. In such a situation, for an engineer to be
able to select the appropriate member size or specify the correct load resisting
performance of a joist, the designer must be able to properly interpret the
manufacturer's allowable load tables and member capacities for both shear and
moment. This course will guide the engineer through that process.
The design
of the overall stability of a building involves an understanding of the load-path
mechanism that distributes the imposed wind or seismic loads from the cladding
to the foundations. Steel joists and joist girders are limited in this regard.
This course will help guide the engineer through the understanding of what these
limitations are.
Course Content
VERTICAL
LOADS
Joist manufacturers recommend
that the most economical option (from a material quantity point of view) for
the support of concentrated or non-uniform loads is to designate the use of
special joists through the use of specific load diagrams. In addition to providing
a load diagram to the manufacturer, it is also recommended that the design engineer
verify that the end seat of the special joist is compatible with the end seat
depth of the adjacent joist series. In general, the maximum shear capacity of
a 2.5 inch deep end seat is limited to about 9.2 kips. End reactions greater
than this will require that the special joist be supplied with a deeper seat.
Alternatives to submitting load diagrams to the manufacturer include:
- Using a heavier standard joist
that is capable of supporting a equivalent uniform load that envelops the
shear and moment diagram for the actual loads imposed
- Specifying a KCS series joist
that provides a shear and moment envelope that is greater than that imposed
by the actual loads
- Substitute a wide flange beam
capable of resisting the imposed loads
Load
diagrams or plans for net uplift loads should always be provided because only
the joist manufacturer is capable of checking members for the stress reversals
associated with these types of vertical loads. The following is an example of
a multi-purpose loading diagram for joists.


In specifying
standard joist sizes as an alternate to special joists, the following precautions
should be taken. The actual uniform load calculated from the load diagram must
fall completely within the equivalent shear diagram of the standard joist selected.
The allowable shear diagram can be constructed from information derived from
the joist load tables and Steel Joist Institute (SJI) specifications. The maximum
allowable end shear is equal to the allowable uniform load times half the span
for a given joist. The allowable shear at the center of the joist is a percentage
of this end shear value. The percentage is given in the SJI specifications for
all joist series available. K series joists are designed for centerline shear
of 25% of the maximum end shear. The point of zero shear for the special load
diagram should also be determined. If this point is not relatively close (one
foot +/-) to the center of the joist span, there may be diagonal members that
are subject to stress reversal. If stress reversal is present with the use of
a standard joist, a KCS series joist must be specified only as an alternate
to the special joist.
Collateral
hanger loads that do not exceed 150# can be accounted for as uniform loading.
When hanger loads exceed 150 pounds, they should be accounted for with special
load diagrams using concentrated loads. An exception to this rule that commonly
occurs includes the support of sprinkler lines, cable trays and ducts. For these
items, it is common for hanger loads to exceed 150#. Joist manufacturers indicate
that for these type of hanger loads, the use of uniform loads to account for
the actual loadings has proved to be reasonable and economical. However, it
is recommended that the design engineer specify on the drawings the hanger spacings
that are required in order to help minimize the magnitude of the reactions.
In addition for these type of hangers, web reinforcement should be employed
for hangers that occur at locations greater than 6" from the bottom chord panel
points.
Typically
the method for determining the proper distribution of loads on a series of adjacent
joists is based on a rigid support transfer element resulting from static equilibrium,
however, there are situations where the elastic nature of the supports and joists
results in a different distribution of the support reactions. The relative stiffness
of a series of joist based on a given distribution beam, RSJ = ((K/S/(4EI))1/4.
Where; K = the individual joist stiffness (kips/inch); S = the joist spacing;
E = the beam modulus; I = the moment of inertia of the beam. If S < (3.14/4
RSJ) the beam on elastic support calculations are applicable. If the spacing
limit is not exceeded and the length of the beam is less than 1/RSJ the beam
may be considered to be rigid with respect to the supporting joists and the
reactions to the joists may be determined by static equilibrium. In lieu of
using spreader beam below or above the joist it is also possible to field fabricate
a truss within and between the joists to distribute the load more effectively
between several members.
Joist
manufacturers recommend that for eccentrically loaded joist girders or beams,
the joist spacing be staggered on each side of the girder by at least 6" to
allow for the bearing seats of the joists to extend past the center line of
the girder. This offsetting helps to compensate for the twisting action induced
on the girder due to differences in joists reactions from opposing sides of
the girder. Extreme situations may actually require the addition of bottom chord
extension bracing from the supported joists to limit the twisting action.
LATERAL
STABILITY & LOADING
The minimum
deck fastening requirements as required by SJI specifications for adequate joist
top chord stability is 100 PLF (300# at 3'-0" o.c.) For K-series joist and from
120 PLF to 250 PLF (depending on the chord size) for LH and DLH joists.
The capacity
of joists and joist girders to function as chord members and collector elements
for diaphragm loadings is discussed extensively in “Designing With Steel Joists,
Joist Girders, Steel Deck” by Fisher, West & Van De Pas. This manual was published
by Nucor Corporation, however it is no longer in publication. Your local joist
manufacturer or steel fabricator may be able to provide you with a used copy.
The following pertinent items are worth noting from this same referenced text.
The maximum chord force permitted by K-series joists is 6.8 kips (see pages
230 and 231).

The maximum
chord force permitted by joist girders weighing more than 30 PLF is 20 kips
(see Table 7.1.1, page 228).

Chord
forces greater than these values can be obtained through extensive modification
to the standard chord/bearing assembly of each section, however, most joist
manufacturers recommend the use of wide flange spandrel beams in lieu of joists
for bracing/chord forces greater than 20 kips. Joist girders can be practically
modified to provide chord force limits of up to 200 kips (see Detail F, pages
93).

For situations
in which the perimeter edge roof angle, acting as a diaphragm collector, is
perpendicular to the span of the joists, the magnitude of the collector force
should be compared to the rollover capacity of the joist seat. The rollover
capacity of a typical is about 1650#. For a typical joist spacing of 6'-0" o.c.,
this capacity would equate to a maximum collector force of 275 PLF. Tests performed
by Vulcraft indicate the actual upper bound of the ultimate rollover strength
limit of some H-series joists was 9.0 kips. Examples of rollover analysis can
be found in Section 7.6, pages 268 through 273.



In either
case, the designer should determine if the magnitude of the collector force
in this situation warrants the use of “drag strut” shear transfer devises such
as that shown in Figures 4.2.8 and 4.2.9, page 70.

Plan, laminated wood and structural
wood fiber decks are not normally used as diaphragms as there has not been adequate
research performed by the industry. Standing seam roofs are also not capable
of functioning as an adequate diaphragm. In all of the above cases, alternate
in-plane horizontal bracing must be provided as a part of the roof system.
For flexible metal deck diaphragms
it should be noted that deck shear capacities tabulated in the Steel Deck Institute
(SDI) Diaphragm Design Manual already take into account the one-third increase
for wind or seismic loads. It is recommended that diaphragm deflections be checked
when used to brace the top of masonry or concrete walls. Deflection equations
are provided in the SDI Diaphragm Manual. It is recommended that the empirical
formula listed on page 63 of this same manual be used as guideline for the limitation
on diaphragm deflection when supporting masonry or concrete walls.
Course Summary
The designer
must compensate for non-uniform loads on joists by developing the shear and
moment diagram for a particular member in order to establish an equivalent uniform
load for use in selecting a standard joist or specify a KCS series joist. A
third alternative involves the development of a loading diagram to enable the
joist manufacturer to design and fabricate a special joist for each load case.
Lateral diaphragm
collector and chord forces must be transmitted between the metal deck and the
lateral resisting system via the joist or joist girder member chords. Standard
joists and joist girders have limited capacities available to accomplish this
goal. Special detailing provisions may be required when the member bearing seat
assembly is not capable of transferring the magnitude lateral loads involved.
Additional
Resource
You
can download a program from Vulcraft's website called Vulcraft Assistant that
helps you design joists with concentrated loads (http://www.vulcraft-in.com/).
The program does not do any deflection calculations.
Related
Links
For additional technical
informaion related to this subject, please visit the following websites or web
pages:
Design/Build
Speeds Construction of New Cold Storage Facility
Steel Joist Institute
Vulcraft
Ten
Situations to Avoid when Designing with Steel Joists
Steel
Solutions Ccenter - Joist the Facts
Up
on the rooftop: How to design and detail non-uniform loads on steel joists
Quiz
Once
you finish studying the
above course content,
you need to
take a quiz
to obtain the PDH credits.

DISCLAIMER:
The materials contained in the online course are not intended as a representation
or warranty on the part of PDHonline.org or any other person/organization named
herein. The materials are for general information only. They are not a substitute
for competent professional advice. Application of this information to a specific
project should be reviewed by a registered professional engineer. Anyone making
use of the information set forth herein does so at their own risk and assumes
any and all resulting liability arising therefrom.